The KET-TAC-000.23 is a closed current transformer for through bars of max size 20x5 mm and for cable of maximum 23 mm.
Ratio 50 ÷ 300/5 A, available in accuracy class 0.5 / 1.
Equipped with 2 insulated screws to ensure a robust and reliable fixing of the current transformer to the through bar and with double connection terminal (connection up to 8 wires) that can be sealed by means of special terminal covers.
Protection Range | IP20 |
Operative Temperature | -25 ÷ +60 °C |
Storage Temperature | -30 ÷ +70 °C |
Relative Humidity | MAX 90% not condensing |
Dimensions | 46 x 65 x 30 mm (W x H x D) |
Mounting | Panel or on DIN-rail |
Cable Diameter | Max 23 mm |
Bar Size | Max 20x5 mm |
Material | ABS, self extinguishing: UL 94 V-O |
Weight | From 150 to 200 g |
Primary Current | 50 ÷ 300 A |
Secondary Current | 5 A |
Precision | 0.5 / 1 |
Working Frequency | 50-60 Hz |
Overload Thermal Current | Typical 100 In/1 s 2.5 Ith |
Highest Voltage for Equipment | 0.72 kV |
Isolation | 3 kV/1 min @ 50 Hz |
Insulation Class | E (max 75 °C) |
Referends Standard | EN61869-2 |
Approvals | CE, cURus and CSA |
Codice | Ratio | Precision | Cable Diameter | Bar Size |
---|---|---|---|---|
KET-TAC-005.23 | 50/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-006.23 | 60/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-007.23 | 70/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-008.23 | 80/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-010.23 | 100/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-012.23 | 120/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-015.23 | 150/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-016.23 | 160/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-020.23 | 200/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-025.23 | 250/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |
KET-TAC-030.23 | 300/5 A | 0.5 / 1 | Max 23 mm | Max 20x5 mm |