The KET-PLC-200 suitable for the management of domotics scenarios and for refrigeration and air conditioning applications.
It has a considerable number of inputs and outputs that allow for a flexible, modular and expandable network of control devices.
The KET-PLC-200 has two RS485 communication ports, ModBUS master or slave, which allow it to be integrated with the other devices of the X-Monitor network.
The installation is foreseen on DIN rail, in a control panel.
Protection Range | Front: IP40; Screw Terminals: IP20 |
Operative Temperature | -10 ÷ +60 °C |
Relative Humidity | MAX 95% not condensing |
Dimensions | 71 x 135 x 60 mm (W x H x D) |
Mounting | DIN-rail |
Required DIN modules | 4 DIN modules |
Electric Board Type | Industrial or switchboard |
Material | Self extinguishing: UL 94 V-O |
Supply Voltage | 24 VAC (50-60 Hz), 35 VA max or 20 ÷ 30 VDC |
Consumption | < 12 W |
Connectors types | Removable terminals |
Battery Type | SuperCap for internal clock function maintenance |
Approximate Battery Life | Keep watch data in the event of power failure for 3 days when the battery is fully charged |
Memory Type | Flash 256 KB; RAM 4 KB |
Supported Protocols | Master or slave ModBUS RTU |
Communication Rate | 100 Kbit/s |
Isolation | Non optoisolated |
Connectors types | Removable terminals |
Digital Inputs | 9 optoisolates at 24 VAC / DC of which 2 up to 2 KHz and 7 at 50-60 Hz |
Analog Inputs | 9 of which 6 for probes PTC / NTC / Pt 1000 / transducers 0-20 mA / 4-20 mA / 0-5 V ratiometric / 0-10 V and 3 for probes PTC / NTC / Pt 1000 |
Resolution | 0.1 °C for probes PTC / NTC / Pt 1000; 0.01 mA for transducers 0-20 mA / 4-20 mA ; 0.01 V for transducers 0-10 V |
Output Type | 6 non-optically isolated outputs: 2 of type PWM / 0-10 V; 2 of type 0-20 mA / 4-20 mA / 0-10 V; 2 of type 0-10 V |
Channels | 7 of type SPST and 2 of type SPDT |
Voltage Output | 250 VAC |
Maximum Rated Current | 3 A |
Isolation | Non optoisolated |
Approvals | CE |