The KET-RKS-200 is a rack monitoring system designed to monitor all basic rack parameters.
The system allows monitoring of rack internal temperatures and PDU consumption. It also has dedicated inputs for smoke, flood and door opening sensors.
Thanks to X-Monitor technology, each rack can be monitored by a Slave unit that communicates to the Master via RS485 serial port.
Equipped with dual 100-240 VAC power supply and supercapacitor to operate even in the absence of power for the time necessary to send the acoustic signal to the alarm.
Internal Flash memory 256 Kb, F-RAM and RTC for data protection.
It is also equipped with an infrared door opening sensor and temperature and relative humidity sensors to check the status of the device itself.
Dimensions | 434 x 40 x 203 mm (W x H x D) |
Mounting | Inside racks 19" |
Material | Case, 19 ", ABS, 1U, Black |
Supply Voltage | Dual 100 ÷ 240 VAC |
Connectors types | Type C14 input connector, panel protection fuses on the back of the case and removable connectors on the PCB |
Battery Type | Supercapacitor to allow the sending of the alarm for power interruption |
Memory Type | Flash 256 KB |
Data Storage Capacity | F-RAM and RTC |
Processor Type | System CPU Micro Atmel ATSAMD21J17A-MU |
Supported Protocols | ModBus Slave connection to an internal or external master |
Connectors types | 2 RJ12 (6P6C) |
Digital Inputs | 4 inputs with automatic presence and sensor type detection, 12 VDC power supply, 4P4C modular connectors |
Analog Inputs | Up to 7 inputs for NTC 10K type temperature probes with RJ45 connectors |
Measure Range | -40 ÷ +123.8 °C |
Precision | ±0.4 ÷ 25 °C |
Repeatability | ±0.1 °C |
Resolution | ±0.01 °C |
Measure Range | 0 ÷ 100%RH |
Precision | ±3%RH from 20 to 80%RH |
Repeatability | ±0.1%RH |
Resolution | ±0.03%RH |
Hysteresis | ±1%RH |
Long Period Stability | <0.5%RH/year |