The KET-TAA-000.50125 is a core-opening current transformer for through-bar of maximum size of 50 x 125 mm.
Ratio 400 ÷ 3200/5 A, accuracy class 1.
Equipped with 10 insulated screws to ensure a robust and reliable fixing of the current transformer to the through bar and with double connection terminal (connection up to 8 wires) that can be sealed by means of special terminal covers.
Protection Range | IP20 |
Operative Temperature | -25 ÷ +50/60 °C |
Storage Temperature | -30 ÷ +70 °C |
Relative Humidity | MAX 90% not condensing |
Dimensions | 106,7 x 177,9 x 60 mm (W x H x D) |
Mounting | Bus-bar |
Bar Size | Max 50x125 mm |
Material | ABS, self extinguishing: UL 94 V-O |
Weight | From 450 to 700 g |
Primary Current | 400 ÷ 3200 A |
Secondary Current | 5 A |
Precision | 1 |
Working Frequency | 48-62 Hz |
Overload Thermal Current | Typical 100 In/1 s 2.5 Ith |
Highest Voltage for Equipment | 0.72 kV |
Isolation | 3 kV/1 min @ 50 Hz |
Insulation Class | E (max 75 °C) |
Referends Standard | EN61869-2 |
Approvals | CE, cURus and CSA |
Codice | Ratio | Precision | Cable Diameter | Bar Size |
---|---|---|---|---|
KET-TAA-040.50125 | 400/5 A | 1 | Max 50x125 mm | |
KET-TAA-050.50125 | 500/5 A | 1 | Max 50x125 mm | |
KET-TAA-060.50125 | 600/5 A | 1 | Max 50x125 mm | |
KET-TAA-070.50125 | 700/5 A | 1 | Max 50x125 mm | |
KET-TAA-075.50125 | 750/5 A | 1 | Max 50x125 mm | |
KET-TAA-080.50125 | 800/5 A | 1 | Max 50x125 mm | |
KET-TAA-100.50125 | 1000/5 A | 1 | Max 50x125 mm | |
KET-TAA-120.50125 | 1200/5 A | 1 | Max 50x125 mm | |
KET-TAA-125.50125 | 1250/5 A | 1 | Max 50x125 mm | |
KET-TAA-150.50125 | 1500/5 A | 1 | Max 50x125 mm | |
KET-TAA-160.50125 | 1600/5 A | 1 | Max 50x125 mm | |
KET-TAA-200.50125 | 2000/5 A | 1 | Max 50x125 mm | |
KET-TAA-250.50125 | 2500/5 A | 1 | Max 50x125 mm | |
KET-TAA-300.50125 | 3000/5 A | 1 | Max 50x125 mm | |
KET-TAA-320.50125 | 3200/5 A | 1 | Max 50x125 mm |