KET-KCO-310 is a kit for measuring thermal energy complete with thermal, thermal/energy to ultrasonic meter based on transit time for flow measurement, KET-CCC-100 computer and PT100 temperature sensors to measure flow and return temperatures.
The KET-KCO-310 displays the energy speed and total energy thanks to the pulse output and through the RS485 interface can communicate with all the devices of the X-Monitor line for energy metering.
Protection Range | IP54 |
Operative Temperature | 0 ÷ +50 °C |
Storage Temperature | -10 ÷ +60 °C |
Relative Humidity | MAX 90% not condensing |
Dimensions | 250 x 48 x 90 mm (W x H x D) |
Mounting | Pipe mounting |
Material | Self-extinguishing: UL 94 V-O |
Supply Voltage | 12 ÷ 24 VAC / VDC |
Consumption | Max 7 VA |
Connectors types | Screw terminal |
Supported Protocols | ModBUS RTU |
Communication Rate | 1.2 ÷ 38.4 Kpbs |
Connectors types | Screw terminal |
Channels | Pulses with amplitude range 3 ÷ 99 ms |
Voltage Output | 48 VAC @ 500 mA; isolated 2500 V |
Measure Range | 0 ÷ +85 °C |
Precision | PT100 Classe B |
Resolution | 0.1 °C |
Principle of Operation | Ultrasonic based on transit time |
Speed Range | 0.1 ÷ 10 m/s bidirectional |
Resolution | ±50 ps |
Repeatability | 0.5% of the measured value |
Precision | 1-3% of flow reading for a flow rate >0.3 m/s |
Measuring Frequency | 200 Hz |
Response Time | 50 ms |
Tube Diameter | DN 22 ÷ 115 mm or 125 ÷ 180 mm |
Referends Standard | 2014/30/EU, 2014/35/EU |
Security | EN61010-1:2010, EN61326-1:2013, EN61326-2-3:2013 |
Metrology | EN1434 |
Codice | Tube Diameter |
---|---|
KET-KCO-310.115 | DN 22 ÷ 115 mm |
KET-KCO-310.180 | DN 125 ÷ 180 mm |