KET-MDC-400 allows the measurement of continuous current up to a maximum of -2500/+2500 A, using a small Hall sensor connected with a comfortable cable length of 2m.
The display, which is equipped, allows the calibration of the sensor through the integrated menu and shows the reading in Ampere, the connection to the network and the quality of the radio signal in real time.
The high sensitivity of the radio module allows to reach distances of over 1000 m in free air.
The LinkQuality function shows on the display the actual quality of the reception allowing a quick positioning of the device.
The KET-MDC-400 is powered by both low voltage and 230 VAC with integrated power supply and can be mounted on both DIN rail and wall.
Protection Range | Front: IP40; Screw Terminals: IP20 |
Operative Temperature | -20 ÷ +60 °C |
Dimensions | 88 x 110 x 60 mm (W x H x D) |
Mounting | Wall mounting or on DIN rail |
Required DIN modules | 5 DIN modules |
Electric Board Type | Industrial or switchboard |
Material | Blend PC/ABS self extinguishing UL94-VO |
Supply Voltage | 12 ÷ 48 VAC, 20 ÷ 60 VDC and 230 VAC with integrated power supply |
Consumption | < 1.5 W @ 12 ÷ 48 VAC / < 1.5 W @ 20 ÷ 60 VDC / < 1.5 W @ 230 VAC |
Connectors types | Screw terminal |
Supported Protocols | X-Monitor Protocol (X-MP) / IEEE 802.15.4 / ZigBee™ Pro 2.0 |
Radio Frequency | 2.4 GHz ISM Band |
Output Power | +3 ÷ +20 dBm |
Sensitivity | -104 dBm |
Antenna Type | RPSMA connector, 90° antenna supplied |
Max Distance (Free Air) | Over 1000 m |
Radio Signal Indicator | Integrated (LinkQuality) |
Output Power Adjustment | From local menu and remotely |
Firmware Upgrade | Via radio |
Sensor Type | Hall effect probe |
Current Range | -2500 ÷ +2500 A |
Typical Sensitivity | 280 V/T |
Linearity | ±0.2% |
Linearity Range | -7.5 +7.5 mT |
Nonlinearity | ±1% |
Temperature Drift | < ±200 ppm/°C |
Noise Spectral Density | <125 nT/sqrt(Hz) (f = 10 Hz ÷ 10 Hz) |