KET-TLP-110 is an environmental sensor capable of detecting the movement of people within a radius of about 3-4 meters. The built-in double light sensor allows you to limit the lighting of lights only below a certain lighting threshold that can be set remotely. The temperature sensor completes the characteristics of the device.
The ModBUS interface allows the connection of the KET-TLP-110 to SCADA systems, programmable logic and standard monitoring systems.
The dry contact input can be used for connecting door / window contacts, PIR sensors or control buttons.
Designed to easily integrate into energy supervision and management systems (BMS / BEMS).
Protection Range | IP40 |
Operative Temperature | -10 ÷ +60 °C |
Storage Temperature | -15 ÷ +60 °C |
Relative Humidity | MAX 80% not condensing |
Dimensions | 100 x 100 x 22.5 mm (W x H x D) |
Mounting | Wall mounted with supplied plate |
Material | ABS, self extinguishing: UL 94 V-O |
Supply Voltage | 5 ÷ 12 VDC |
Connectors types | Removable spring clamps |
Supported Protocols | ModBUS RTU Slave |
Communication Rate | 9.6, 19.2, 38.4 o 57.6 Kpbs |
Connectors types | Removable spring clamps |
Channels | 1 for dry contact with detection time at contact variation of about 50ms. |
Output Power Adjustment | From remote |
Firmware Upgrade | Via USB C connector |
Support for public environment | Anti-removal support, keyboard lock |
Sensor Type | NTC or digital (Only .TH version) |
Measure Range | -40 ÷ +123.8 °C |
Precision | ±0.4 ÷ 25 °C |
Repeatability | ±0.1 °C |
Resolution | ±0.01 °C |
Version | Only .TH version |
Measure Range | 0 ÷ 100%RH |
Precision | ±3%RH from 20 to 80%RH |
Repeatability | ±0.1%RH |
Resolution | ±0.03%RH |
Hysteresis | ±1%RH |
Long Period Stability | <0.5%RH/year |
Number of sensors | 2, on front and on top |
Measure Range | 10 ÷ 1000 Lux |
Response Curve | Similar to that of the human eye |
Measurand | Up to 4 m; Recommended 0 ÷ 3.5 m |
Viewing Angle | <=100° cone angle, distance <=4m |