KET-M is a DC-301 Direct Current energy analyzer unit with built-in 6 digit display and programming push-button, particularly indicated for DC current, voltage, power and energy metering. Direct connection up to 20 A and with external shunt up to 1000 A. Moreover the unit is provided with an auxiliary serial communication bus which is connected to the VMU-X unit so to provide an RS485 communication port. Housing for DIN-rail mounting, IP40 (front) protection degree.
KET-MDC-301 can be connected to the Master ModBUS wireless KET-RMB-211 or directly to the Gateway X-Monitor.
Protection Range | Front: IP40; Screw Terminals: IP20 |
Operative Temperature | -25 ÷ +55 °C |
Storage Temperature | -30 ÷ +70 °C |
Relative Humidity | MAX 90% not condensing |
Dimensions | 35 x 90 x 67 mm (W x H x D) |
Mounting | DIN-rail |
Required DIN modules | 2 DIN modules |
Electric Board Type | Industrial or switchboard |
Material | Noryl, self extinguishing: UL 94 V-O |
Supply Voltage | 38 ÷ 265 VAC / VDC (45-65 Hz) |
Consumption | <= 1.5 W; <= 3 VA |
Connectors types | Screws terminal: min. 2.5 mm², max 6 mm² in case of flexible wire, Max. 10 mm² in case of rigid wire. Min./Max. screws tightening torque: 0.5 Nm / 1.1 Nm |
Insertion Types | 3/4 wires depending on the type of connection |
Connection | Direct or external shunt |
Maximum Rated Current | Continuous up to 20 A for 1s, external shunt up to 1000 A |
Accuracy | ±0.5 RDG |
Connections | Screw 1.5 mm². Tightening torque: 0.4 Nm / 0.8 Nm |
ESD Protection | 4 kV |
Configuration | By keyboard |
Supported Protocols | ModBUS RTU |
Communication Rate | Max 115 Kbps |
Isolation | Class III |
Connectors types | Screw terminal |
Channels | 1 Selectable either for pulse transmission proportional to the energy being measured or for alarm control on selected variable |
Digital Inputs | Static type: opto-mosfet. load Von 2.5 VAC/DC max 70 mA, Voff 260 VAC/DC max |
Voltage Inputs | 500 V |
Current Inputs | Direct 20 ADC, External Shunt 10 VDC, DC External Sensor 50 VDC |
Approvals | CE, cULus listed |
Security | EN61000-6-2, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-6, EN61000-4-5, EN61000-6-3 |
Metrology | IEC60664, IEC61010-1 EN60664 |